Heat Pump Sizing
Heat pump sizing from the building heat load: required output incl. hot water and utility blocking times, bivalence point from the manufacturer capacity curve, GModG hybrid share and BEG efficiency checks, annual electricity estimate. Required heating output = (design heat load + mean hot-water load) x 24 / (24 - blocking hours). Hot water energy per day = volume x density (Kell 1975) x 4.18 kJ/(kg K) x temperature rise.
POST https://rechen.halowerk.com/v1/heat-pump-sizing
0.003 USDC on Base · payTo 0x2880EdfFF13100677Bf97A3CBdF3Bc34771C4E5E
Status: verified · payable
Operator badge: embed this endpoint's live status badge — it reads "Verified Payable" only while the probe record backs it.
Settlement: direct to the seller's payTo — 0% HIVE402 take
Payment routes
{
"blocking_hours_per_day": 2,
"capacity_curve": [
{
"capacity_kw": 5,
"outdoor_c": -15
},
{
"capacity_kw": 6,
"outdoor_c": -7
},
{
"capacity_kw": 7.5,
"outdoor_c": 2
},
{
"capacity_kw": 8.5,
"outdoor_c": 7
}
],
"design_heat_load_kw": 8,
"design_outdoor_temp_c": -12,
"hot_water": {
"litres_per_day": 200
}
}{
"limitations": [
"Information computed by formula and statutory rules from the stated parameters; not legal, tax, funding or energy advice and no substitute for planning by a qualified professional.",
"The heat load, design outdoor temperature and capacity data are inputs; the linear load line ignores solar and internal gains below the heating limit.",
"Seasonal performance and coverage shares need a climate-based method (e.g. VDI 4650) that is not reproduced here."
],
"result": {
"assumptions": [],
"bivalence_point_c": -5.88,
"blocking_factor": 1.0909,
"capacity_at_design_kw": 5.375,
"checks": [],
"design_coverage_percent": 67.2,
"design_heat_load_kw": 8,
"hot_water": {
"energy_kwh_per_day": 9.286,
"mean_load_kw": 0.3869
},
"legal_basis": {
"checked": "2026-11-01",
"norms": [
"§ 43(5) GModG",
"BEG EM TMA Nr. 3.4"
],
"parameters_valid": {
"beg_from": "2026-07-21",
"beg_to": "2030-12-31"
},
"sources": [
"https://www.gesetze-im-internet.de/geg/",
"https://www.bundesanzeiger.de/pub/publication/jLXvW09kHTQoDINAdoC/content/jLXvW09kHTQoDINAdoC/BAnz%20AT%2027.08.2026%20B1.pdf?inline"
],
"version": "GModG as amended 23.07.2026; BEG EM guideline of 17.08.2026 (BAnz AT 27.08.2026 B1)"
},
"load_line": {
"design_outdoor_c": -12,
"heating_limit_c": 15,
"load_at_2_kw": 3.8519,
"load_at_7_kw": 2.3704,
"load_at_minus_7_kw": 6.5185
},
"required_output_kw": 9.149,
"steps": [
"Required output = (8 + 0.3869) x 24/(24 - 2) = 9.149 kW.",
"Load line: 8 kW at -12 °C to 0 at 15 °C; bivalence point where capacity = load: -5.88."
]
},
"service": "heat-pump-sizing",
"status": "success"
}Script Master Labs LLC · SDVOSB · Kinston, NC · Terms · Refunds · Privacy · Sellers · Contact
SML network: ScriptMasterLabs — the main site · SML Dual Market — the human store: human checkout, card & crypto · VA Ratings — VA disability ratings, free for veterans
Agent intel 
| Trust score | pending / 100 · breakdown |
|---|---|
| Probe uptime (30d) | — over 0 probes · daily |
| Avg 402 latency | — ms |
| Paid calls (30d, on-chain) | 0 calls · 0 buyers |
How to call
POST https://rechen.halowerk.com/v1/heat-pump-sizing · input in body · spec from live-challenge
Input schema
{
"type": "object",
"additionalProperties": false,
"required": [
"design_heat_load_kw",
"design_outdoor_temp_c"
],
"properties": {
"design_heat_load_kw": {
"type": "number",
"exclusiveMinimum": 0,
"maximum": 10000
},
"design_outdoor_temp_c": {
"type": "number",
"minimum": -30,
"maximum": 5
},
"heating_limit_temp_c": {
"type": "number",
"minimum": 8,
"maximum": 20,
"default": 15
},
"hot_water": {
"type": "object",
"additionalProperties": false,
"required": [
"litres_per_day"
],
"properties": {
"litres_per_day": {
"type": "number",
"minimum": 0,
"maximum": 100000
},
"hot_c": {
"type": "number",
"minimum": 30,
"maximum": 80,
"default": 50
},
"cold_c": {
"type": "number",
"minimum": 0,
"maximum": 25,
"default": 10
},
"loss_factor": {
"type": "number",
"minimum": 1,
"maximum": 3,
"default": 1
}
}
},
"blocking_hours_per_day": {
"type": "number",
"minimum": 0,
"maximum": 12,
"default": 0
},
"capacity_curve": {
"type": "array",
"minItems": 2,
"maxItems": 20,
"items": {
"type": "object",
"additionalProperties": false,
"required": [
"outdoor_c",
"capacity_kw"
],
"properties": {
"outdoor_c": {
"type": "number",
"minimum": -30,
"maximum": 30
},
"capacity_kw": {
"type": "number",
"minimum": 0,
"maximum": 10000
}
}
}
},
"hybrid": {
"type": "object",
"additionalProperties": false,
"required": [
"capacity_point_a_kw",
"peak_generator_kw",
"operation"
],
"properties": {
"capacity_point_a_kw": {
"type": "number",
"minimum": 0,
"maximum": 10000
},
"peak_generator_kw": {
"type": "number",
"exclusiveMinimum": 0,
"maximum": 10000
},
"operation": {
"type": "string",
"enum": [
"parallel",
"partly_parallel",
"alternative"
]
}
}
},
"annual_heat_demand_kwh": {
"type": "number",
"minimum": 0,
"maximum": 100000000
},
"seasonal_performance_factor": {
"type": "number",
"minimum": 1,
"maximum": 10
},
"refrigerant_natural": {
"type": "boolean"
},
"heat_source": {
"type": "string",
"enum": [
"air",
"ground",
"water",
"other"
]
},
"etas_35_percent": {
"type": "number",
"minimum": 50,
"maximum": 400
},
"etas_55_percent": {
"type": "number",
"minimum": 50,
"maximum": 400
},
"low_temperature_heat_pump": {
"type": "boolean",
"default": false
},
"installation_year": {
"type": "integer",
"minimum": 2024,
"maximum": 2035
}
}
}curl -i -X POST 'https://rechen.halowerk.com/v1/heat-pump-sizing' \
-H 'content-type: application/json' -d '{"design_heat_load_kw":8,"design_outdoor_temp_c":-12,"hot_water":{"litres_per_day":200},"blocking_hours_per_day":2,"capacity_curve":[{"outdoor_c":-15,"capacity_kw":5},{"outdoor_c":-7,"capacity_kw":6},{"outdoor_c":2,"capacity_kw":7.5},{"outdoor_c":7,"capacity_kw":8.5}]}'
Agents: POST https://hive402.scriptmasterlabs.com/mcp → route_task / proxy_call · SDK /sdk/hive402.mjs